Sheet Last Modified: 04-23-2021    
School:  Haverford Child Development Center
Vendor: Devine Test 1 Devine Test 2
Please visit https://bit.ly/3mA7rMY for more information on how to read this report.
Classroom ID / Area ID Number Classroom / Area Type supplied  Actual Mechanical System Outside Air CFM (OA) Mechanical System Occupancy (OA CFM / 15) Active Pure Unit Installed Classroom / Area Square Footage Square Footage Occupancy (SqFt / 44) Maximum Occupancy per Room Type of Unit
2 Classroom 291.0 19 Yes 1058 24 24 Rooftop Unit
3 Classroom 323.0 21 Yes 1058 24 24 Rooftop Unit
4 Classroom 277.0 18 Yes 1058 24 24 Rooftop Unit
5 Classroom 374.0 24 1058 24 24 Rooftop Unit
5A Office 15.0 1 170 3 1 Rooftop Unit
6 Conference 418.0 27 621 14 14 Rooftop Unit
7 Conference 415.0 27 621 14 14 Rooftop Unit
8 Classroom 287.0 19 560 12 12 Rooftop Unit
8A Office 336.0 22 210 4 4 Rooftop Unit
9 Classroom 723.0 48 962 21 21 Rooftop Unit
10A Lounge 34.0 2 216 4 2 Rooftop Unit
10B Book Storage 11.0 0 288 6 0 Rooftop Unit
- Gym 1,065.0 71 2204 50 50 Rooftop Unit
- Lobby 18.0 1 608 13 1 Rooftop Unit
- Storage 89.0 5 572 13 5 Rooftop Unit
- BE Office 18.0 1 128 2 1 Rooftop Unit